2 ) overvoltage – GE Industrial Solutions AF-300 MICRO-$AVER II User Manual

Page 70

Advertising
background image

8-3

O U

The power
supply
voltage
should be
corrected.

Yes

Yes

No

Will fault take place when the load is removed suddenly?

Is the power supply voltage within the specified limits?

No

Was DC bus voltage above alarm level when alarm occurred?

No

Yes

Can the deceleration time be
increased?

Review the control and system application again. Contact GE Fuji
Electric.

Is a braking resistor installed and activated?

No

Increase
the timed
setting

Decrease until the
failure does not
occur.

No

Yes

No

Yes

No

Yes

Can the acceleration time be
increased?

Can the load inertia be decreased?

No

Yes

Yes

Investigate braking
resistor for correct
connection rating and
control settings.

Does action take place after
rapid acceleration is completed?

Yes

( 2 ) Overvoltage

Possible Drive
failure or
malfunction due
to electrical
noise. Contact
GE Fuji Electric.