CAUTION:

1. The Control Circuit Terminal wiring should be kept as far as possible from the main circuit wiring to prevent

operation error due to noise interference. Never install them in the same duct or conduit. A separation distance
of 4 inches or more is recommended. If the control circuit wiring must cross the main circuit wiring, make sure
it crosses at a right angle.

2. Use shielded wire for the control circuit wiring, which should be as short as possible (66 feet or less). Connect

shield to the Drive ground terminal and leave the other end open but taped.

3. Install a surge protector in parallel with any magnetic contactors, solenoids, relays or timer coils which are close

to the Drive.

Figure 4-6. WIRING DIAGRAM

#

X4(HLD)

RST

BX

Y1

PLC

PROGRAMMABLE LOGIC
CONTROL POWER

ALARM RELAY OUTPUT

FUSE

DIGITAL METER

BRAKING RESISTOR

1/2 TO 5HP #

P1

DC REACTOR #

DO NOT CONNECT
TO CM

1 or 3PH
50/60 Hz
230/480 Vac

(Based on
Model selected)

* Terminal 11 should not be connected to CM.

L3 not supplied on single phase units.

# Optional

BRAKING RESISTOR

THERMAL SWITCH

GROUND

DISCONNECT/
CIRCUIT
BREAKER #

ANY ADDITIONAL NORMALLY
CLOSED PROTECTIVE
INTERLOCKS SHOULD BE
ADDED IN SERIES