External Power

5-7

5. Connect the wires from the external power cable to the DC

power source, observing the labels on the external power cable,
in the following configuration:

Green/WhiteNegative (–)

Red/BlackPositive (+)

Warning: Turn off power to the DC power source before
connecting the External Power cable wires.

6. Turn on power to the DC power source and test FlowShark

monitor by calling the FlowShark monitor using the
Diagnostics feature of the Profile

®

software. Perform a

Monitor Status and verify that the monitor battery voltage is
approximately 12 volts. Refer to Chapter 6, Configuration and
Activation
, for additional information.

Upgrade Kit to Convert from Battery Power to
External Power

For existing FlowShark installations with battery power,
modifications are required to the monitor before external power can
be connected. An upgrade kit must be ordered (ADS p/n 5000-
0730). Detailed instructions are included in the kit to perform the