Alpha cable type – ADS Environmental Services FlowShark QR 775002 A4 User Manual

Page 198

Advertising
background image

Analog Input/Output Installation and Configuration 8-11

ALPHA Cable Type

Pin Pair Wire Color

1

Function

Notes

A

1

Shield

Analog Input Channel #1
Ground

Connect to shield of end-
run cable

B

1

Red

Channel #1 4-20mA Input +

C

1

Black

Channel #1 4-20mA Input -

D

2

Shield

Analog Input Channel #2
Ground

Connect to shield of end-
run cable

E

2

White

Channel #2 4-20mA Input +

F

2

Black

Channel #2 4-20mA Input -

G

3

Black

0 - 5 VDC Output #1

Jumper Selectable,
default is 4-20mA output

H

4

Blue

+24VDC Power (for Output
#1

2

+24VDC not needed if
user supplies loop power

J

4

Black

Output #1 Ground

K

3

Green

4-20mA, Output #1

L

5

Black

0 - 5 VDC Output #2

Jumper Selectable,
default is 4-20mA output

M

6

Yellow

+24VDC Power (for Output
#2)

2

+24VDC not needed if
user supplies loop power

N

6

Black

Output #2 Ground

P

N/C

N/A

N/A

R

5

Brown

4-20mA, Output #2

1

This represents the color wire inside the associated pair.

2

+24VDC power for outputs 1 and 2 can be common if isolated operation is not required.

Advertising