ADS Environmental Services FlowShark QR 775002 A4 User Manual

Page 234

Advertising
background image

10-22 ADS FlowShark Manual

Problem

Raw ultrasonic depth data shows depths greater than
the pipe diameter.

Possible

Causes

Temperature or physical offsets may be incorrect.

Pipe height may be incorrect.

Pipe may be surcharged.

Ultrasonic depth sensor may be dirty.

Ultrasonic depth sensor may be faulty.

Possible

Solutions

Verify the physical and temperature offsets.

Verify the pipe height.

Clean the ultrasonic depth sensor.

Replace the ultrasonic depth sensor.

Contact your regional ADS representative.

Problem

Depth data indicates a surcharged pipe, but the pipe is
free flowing.

Possible

Causes

Temperature or physical offsets may be incorrect.

Pipe height may be incorrect.

Ultrasonic depth sensor may be dirty.

Ultrasonic depth sensor may be faulty.

Analog board may be faulty.

Possible

Solutions

Verify the temperature and physical offsets.

Verify the pipe height.

Clean the ultrasonic depth sensor.

Contact your regional ADS representative.

Replace the ultrasonic depth sensor.

Replace the monitor if defective.

Advertising