Modbus

9-5

Defining the Modbus Register Values

Use the information provided in the following table to select the
FlowShark output values to be received by the control system. This
table contains the most commonly configured value names and
associated register addresses.

Holding Register Definitions

Description

Profile

®

Entity

Units of Measure

Registers

Flow

FLOW1

(QCONTINUITY)

MGD

40001-40002

UniDepth

UNIDEPTH

Inches

40005-40006

Ultrasonic Depth

UDEPTH

Inches

40007-40008

Pressure Depth

PDEPTH

Inches

40053-40054

Peak Velocity

RAWVEL

FPS

40003-40004

Average Velocity

N/A (VELOCITY)

FPS

40061-40062

Rain Intensity

RAINI

Inches/Unit Time

40019-40020

Rain

RAIN

Inches

40031-40032

Number of
Samples

SAMPLES

N/A

40077-40078

Analog Input 1

Varies

Varies

40087-40088

Analog Input 2

Varies

Varies

40089-40090

Analog Output 1

Varies

Varies

40091-40092

Analog Output 2

Varies

Varies

40093-40094

Monitor Battery

BTYVOLT

Volts

40025-40026

Radio Battery

BTY_RADIO

Volts

40029-40030

Additional entities and values are available. Refer to Appendix C,
Modbus Output Registry Entities and Values, for a complete list.