Output assign – Nor-Cal SDC15 Controller User Manual

Page 104

Advertising
background image

Output assign

The assign of four inputs (A, B, C, D) used for the output bit function can be set.

5-54

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Setting display/bank)

Display

Contents

Initial value

User level

Control output 1 Output
assign A (Setup setting/DO
Assignment bank)

0: Normally opened. (OFF, 0)
1: Normally closed. (ON, 1)
2: Internal Event 1
3: Internal Event 2
4: Internal Event 3
5: Internal Event 4
6: Internal Event 5
7 to 13: Undefined.
14: MV1
15: MV2
16 to 17: Undefined.
18: DI1
19: DI2
20 to 25: Undefined.
26: Internal Contact 1
27: Internal Contact 2
28: Internal Contact 3
29 to 33: Undefined.
34: Communication DI1
35: Communication DI2
36: Communication DI3
37: Communication DI4
38: MANUAL mode
39: READY mode
40: Undefined.
41: AT running
42: During SP ramp
43: Undefined.
44: Alarm occurs. (

AL0 1

to

AL99

)

45: PV alarm occurs. (

AL0 1

to

AL03

)

46: Undefined.
47: mode key pressing status
48: Event output 1 status
49: Control output 1 status

14

High function

Control output 1 Output
assign B (Setup setting/DO
Assignment bank)

0

Control output 1 Output
assign C (Setup setting/DO
Assignment bank)

0

Control output 1 Output
assign D (Setup setting/DO
Assignment bank)

0

Control output 2 Output
assign A (Setup setting/DO
Assignment bank)

15

Control output 2 Output
assign B (Setup setting/DO
Assignment bank)

0

Control output 2 Output
assign C (Setup setting/DO
Assignment bank)

0

Control output 2 Output
assign D (Setup setting/DO
Assignment bank)

0

Event output 1 Output
assign A (Setup setting/DO
Assignment bank)

2

Event output 1 Output
assign B (Setup setting/DO
Assignment bank)

0

Event output 1 Output
assign C (Setup setting/DO
Assignment bank)

0

Event output 1 Output
assign D (Setup setting/DO
Assignment bank)

0