Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Operation type

Set value

Direct action

Reverse action

of operation

type

Loop diagnosis 3

22

High limit

Low limit

Time

Conditions 3

ON delay

set time

Conditions 3

ON delay

set time

ON delay is started when conditions 1 and 2 are satisfied.

Area satisfying

conditions 2

Area satisfying

conditions 2

Time

Time

PV

MV

EV

ON

ON

HYS

HYS

PV to be used

as reference

PV to be used as reference

(0 or more)

Main setting

Main setting (0 or more)

Area satisfying

conditions 1

Area satisfying

conditions 1

High limit

Low limit

Time

Conditions 3

ON delay

set time

Conditions 3

ON delay

set time

ON delay is started when conditions 1 and 2 are satisfied.

Area satisfying

conditions 2

Area satisfying

conditions 2

Time

Time

PV

MV

EV

ON

ON

HYS

HYS

(0 or more)

Main setting

Main setting (0 or more)

Area satisfying

conditions 1

Area satisfying

conditions 1

PV to be used

as reference

PV to be used

as reference

The event is turned ON when any change in PV corresponding to increase/decrease in MV
(Manipulated variable) is not observed. This event is used to detect any fault at the operation
end.

Setting items
• Main setting: Change in PV from the point that the MV reaches the high limit (100%) or low

limit (0%).

• Sub-setting: Range of absolute value of deviation (PV-SP) allowing the event to turn OFF.
• ON delay time: Diagnosis time
• OFF delay time: A period of time from power ON allowing the event to hold OFF state.

Operation specifications
The direct action is used for the heat control and is turned ON in the following cases:
• The increase in PV becomes smaller than the main setting after the diagnosis time (ON

delay time) has elapsed after the MV had reached the high limit.

• The decrease in PV becomes smaller than the main setting after the diagnosis time (ON

delay time) has elapsed after the MV had reached the low limit.

The reverse action is used for the cool control and is turned ON in the following cases:
• The decrease in PV becomes smaller than the main setting after the diagnosis time (ON

delay time) has elapsed after the MV had reached the high limit.

• The increase in PV becomes smaller than the main setting after the diagnosis time (ON

delay time) has elapsed after the MV had reached the low limit.

In the following cases, the event is turned OFF with the priority over the above conditions:
• The absolute value of the deviation (PV-SP) becomes less than the sub-setting.

However, the event is turned OFF when the absolute value of the deviation is less than the
(sub setting – hysteresis) value after the absolute value of the deviation has become the sub
setting or more.

• A period of time after the operation has been started by power ON is less than the OFF

delay time.

CAUTION
When setting the ON delay and OFF delay, it is necessary to put in " High function
configuration".
The default settings of the ON delay and OFF delay before shipment are 0.0s.