13-3

Chapter 13. SPECIFICATIONS

Current transformer input

Number of
input points:

2 points

Input object:

Current transformer with 100 to 4,000 turns (availability is by 100-turn
units)
Optional unit Model No.: QN206A (800 turns, hole diameter: 5.8 mm)
Optional unit Model No.: QN212A (800 turns, hole diameter: 12mm)

Current measurement
lower limit:

0.4Aac (800 turns, 1 time)
Formula; Number of turns ÷ (2000 x number of power wire loops)

Current measurement
upper limit:

50.0Aac (800 turns, 1 time)
Formula; Number of turns ÷ (16 x number of power wire loops)

Allowable measured
current:

70.0Aac (800 turns, 1 time)
Formula; Number of turns ÷ (16 x number of power wire loops) x 1.4

Display range lower
limit:

0.0Aac

Display range upper
limit:

70.0Aac (800 turns, 1 time)
Formula; Number of turns ÷ (16 x number of power wire loops) x 1.4

Display accuracy:

±5%FS

Display resolution:

0.1Aac

Event relay output

Number of output
points:

0 to 3 points (This may vary depending on the model.)

Output type:

SPST contact 3 points, Common 2 points, Each individual point

Output rating:

250Vac/30Vdc, 2A (Resistance load)

Service life:

100,000 cycles or more

Min. open/close
specifications:

5V, 10mA (Reference value)

RS-485 communication

Transmission line:

3-wire method

Transmission speed:

4800, 9600, 19200, 38400 bps

Communication
distance:

Max. 500m

CPL/MODBUS:

Half duplex, start/stop synchronization method

Communication
protocol:

In conformity with CPL and MODBUS

Number of
connection units:

Max. 31 units

Terminating resistor:

Connection prohibited.

Loader communication

Transmission line:

3-wire method

Transmission speed:

Fixed at 19200 bps.

Recommended cable: Specially designed cable, 2m Model No.: 81440793-001