5-41

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Operation type

Set value

Direct action

Reverse action

of operation

type

Loop diagnosis 1

20

Sub-setting

Main setting

Time

Conditions 3

ON delay

set time

ON delay is started when conditions 1 and 2 are satisfied.

Area satisfying

conditions 1

Area satisfying

conditions 2

Time

Time

PV

MV

EV

ON

HYS

Sub-setting

Main setting

Time

Conditions 3

ON delay

set time

ON delay is started when conditions 1 and 2 are satisfied.

Area satisfying conditions 1

Area satisfying

conditions 2

Time

Time

PV

MV

EV

ON

HYS

The event is turned ON when any change in PV corresponding to increase/decrease in MV
(Manipulated variable) is not observed.
This event is used to detect any fault at the operation end.

Setting items
• Main setting: MV (Manipulated variable)
• Sub-setting: PV
• ON delay time: Diagnosis time

Operation specifications
The event is turned ON when the value does not reach the PV set in the sub-setting within
the diagnosis time (ON delay time) (conditions 1) even though the MV exceeding the main
setting is held (conditions 2).

CAUTION
When setting the ON delay, it is necessary to put in "High function configuration".
The default setting of the ON delay before shipment is 0.0s.

Heat control

Cool control

*

: When the event type is CT1/2 heater burnout/over-current or CT1/2 heater short-circuit,the status becomes that

the event judgment cannot be made from the time of power ON until that CT input current value is measured for
the first time. In this case, the internal event output is OFF for both of direct action and reverse action in the
direct/reverse setting. To avoid that the output becomes OFF at power ON when used in reverse action, set as
follows:
(Setting example)
For direct/reverse setting of CT1/2 heater burnout/over-current or CT1/2 short-circuit event, select the direct
action, and set the reverse operation in DO assignment calculation of the event output terminal (event terminal or
control output terminal).

CT event(direct action)

[Reverse]

(DO output)

Normally open(0)

Normally open(0)

Normally open(0)

Advertising