Nor-Cal SDC15 Controller User Manual

Page 203

Advertising
background image

11-3

• The PV input type is T (thermocouple).

• The PV input type is R (RTD).

• The PV input type is L (DC voltage/DC current).

(5) Keep the apply status for approximately 30 sec.

(6) Click

[Write]

.

(7) Return to step (2) until the final gain No. is completed.

Handling Precautions

• In the PV input calibration, always adjust all gains.

• Do not leave the PV input terminal open during heat-up between

power ON of this unit and starting of calibration. When the input type

is thermocouple or DC voltage, put the unit in the 0V-input (or

terminals are short-circuited) status. When the input type is RTD, put

the unit in the 100

-input (or terminals are short-circuited) status.

Chapter 11. CALIBRATION

Voltage

generator

This unit

-

+

(4)

(5)

(6)

Resistor

This unit

(4)

(5)

(6)

Voltage

generator

Gain Nos. 1 to 12 (voltage)

This unit

-

+

(4)

(5)

(6)

Current

generator

Gain Nos. 13 to 16 (current)

This unit

-

+

(4)

(5)

(6)