Pid bank, Bank selection – Nor-Cal SDC15 Controller User Manual

Page 139

Advertising
background image

6-5

Chapter 6. LIST OF DISPLAYS AND SETTING DATA

PID bank

Bank selection:

Display

Item

Contents

Initial
value

User
level

Remarks

P (Proportional band)

0.1 to 999.9%

5.0

0

MV low limit

0.0

1

Displayed when the control
method is other than the
ON/OFF control (CtrL

0).

-10.0 to +110.0%

Displayed when the control
method is other than the
ON/OFF control (CtrL

0).

P (Proportional band)
(cool)

5.0

0

0.1 to 999.9%

Displayed when the control
method is other than the
ON/OFF control (CtrL

0) and

the Heat/Cool control is used
(C26 = 1).

I (Integral time)
(cool)

120

0

0 to 9999s
(No integration control action when
set at "0".)

D (Derivative time)
(cool)

30

0

0 to 9999s
(No derivative control action when
set at "0".)

I (Integral time)

0 to 9999s
(No integration control action when
set at "0".)

120

0

D (Derivative time)

0 to 9999s
(No derivative control action when
set at "0".)

30

0

Manual reset

-10.0 to +110.0%

50.0

0

Displayed when the control
method is other than the
ON/OFF control (CtrL

0) and

the I (Integral time) (I-1) is
“0”.

MV high limit

100.0

1

-10.0 to +110.0%

Output low limit (Cool)

0.0

1

-10.0 to +110.0%

Output high limit
(Cool)

100.0

1

-10.0 to +110.0%