Mv scaling range – Nor-Cal SDC15 Controller User Manual

Page 118

Advertising
background image

MV scaling range

When the control output type is set to either SP+MV or PV+MV, the control

output is a continuous output in which the amount of change in the MV is added to

the SP or PV.

• When the output type of control output 1, control output 2 or the auxiliary output

is SP+MV or PV+MV, this item is displayed and can be set.

• The value calculated by the following formula is output according to the output

scaling low/high limit settings:

In case of SP+MV,(MV-50.0)/100.0 x MV scaling range + SP

In case of PV+MV,(MV-50.0)/100.0 x MV scaling range + PV

Handling Precautions

• This function is used for cascade control when the continuous output

of this controller is connected to the RSP (remote SP) of another

controller, with this controller as master and the other controller as

slave. Set the RSP range to MV scaling range, which changes in

proportion to a change in the MV (0–100%) of this controller.

• If ROM version 1 of the instrument information bank(

Id02

) is prior to

version 2.04, neither SP+MV nor PV+MV can be selected as an

output type. The MV scaling range is not displayed and cannot be set.

5-68

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Bank)

Display

Contents

Initial value

User level

Control output 1 MV scaling
(Setup bank)

0 to 9999
The decimal point position and unit are same
as those of the PV input range type.

200

Simple,
Standard,
High function

Control output 2 MV scaling
(Setup bank)

200

Auxiliary output MV scaling
(Setup bank)

200

output(%)

Scaling high limit

A change of MV

An example of the output type is SP+MV

A change of output
depend on MV

Input

0

-10

Scaling low limit

0% 50% 100%

110
100

SP

MV

scaling range