7-11

Fixed length random data write command (WU command)

This command writes data to random (non-continuous) addresses in two-byte

units. Data is expressed as four hexadecimal digits.

Send message

Data is sent for the specified write data count with the data address (four

hexadecimal digits) of the data to be written and the data (four hexadecimal digits)

as a pair.

Response message

If writing is successful, the normal termination code (two decimal digits) is

returned. If only part of the data is written, and the remaining data is not written,

the warning termination code (two decimal digits) is returned. If none of the data

is written, the abnormal termination code (two decimal digits) is returned.

Maximum write data count per message

Up to 14 words for both RAM and EEPROM area

Chapter 7. CPL COMMUNICATIONS FUNCTIONS

0 0

W

(1)

U

(3)

(5)

(6)

(2)

(4)

(1) Fixed length random data write command
(2) Sub-command: fixed to "00".
(3) Data address 1
(4) Write data 1
(5) Data address (n)
(6) Write data (n)

• Normal termination

0

(1)

0

• Abnormal termination or warning

X

(1)

X

The abnormal termination code is entered at XX.
For details of codes,
refer to

7-6, List of Termination Codes (on page 7-14).

(1) Termination code