Sp up ramp/down ramp, Sp low limit/high limit – Nor-Cal SDC15 Controller User Manual

Page 80

Advertising
background image

SP up ramp/down ramp

The SP up ramp and down ramp can be set.

• When an initial value of “0.0U” is set, the SP ramp function does not function.

Therefore, when the up ramp setting is set to “0.1U” or more and the down ramp
is set to “0.0U”, the SP ramp functions only during SP up and the SP ramp does
not function during SP down. Additionally, the reverse operation can also be set
so that the SP ramp functions only during SP up and it does not function during
SP down.

• "0.1U" shows that the decimal point position of the PV is shifted one digit

rightward.

Example: When the thermocouple input is in a range of -200 to +1200˚C, "0.1U"

is "0.1˚C ".

Example: When the DC voltage input is in a range of 0.0 to 100.0, "0.1U" is

"0.01".

• The ramp is started assuming that the current PV value is used as start point

when any of the following conditions is satisfied:

The power is turned ON.
READY+AUTO status is changed to RUN+AUTO status.
RUN+MANUAL status is changed to RUN+AUTO status.
The AT function is completed (both normal end and forced stop).

SP low limit/high limit

The SP low limit and high limit can be set to limit the SP range.

Handling Precautions

When the PV input range type (setup C01) is set, the SP low limit and

high limit are initialized.

5-30

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Setting display/bank)

Display

Contents

Initial value

User level

SP up ramp
(Parameter
setting/Parameter bank)

0.0U:

No ramp

0.1 to 999.9U
(The unit of the ramp time is selected using
the SP ramp unit.)

0.0U

High function

0.0U

SP down ramp
(Parameter
setting/Parameter bank)

Item (Setting display/bank)

Display

Contents

Initial value

User level

SP low limit
(Setup setting/Setup bank)

PV input range low limit to PV input range
high limit

PV input range low
limit

Standard,
High function

SP high limit
(Setup setting/Setup bank)

PV input range low limit to PV input range
high limit

PV input range high
limit

Standard,
High function