Control action and Heat/Cool control

The control action (direct/reverse) and Heat/Cool control (enabled/disabled) can
be selected.

• When the control method is other than the ON/OFF control (CtrL ≠ 0),

[Heat/Cool control: C26] can be displayed and set.

• When the Heat/Cool control is set disabled (C26 = 0), [Control action: C14] can

be displayed and set.

• When the Heat/Cool control is set enabled (C26 = 1), the control action is

changed to the reverse action (C14 = 0), the preset MANUAL value (C20) is
changed to "50.0", and the initial output of PID control (C22) is changed to
"50.0".

• The reverse action (heat control) is a control that decreases (or turns OFF) the

manipulated variable (MV) as the PV increases.
The direct action (cool control) is a control that increases (or turns ON) the
manipulated variable (MV) as the PV increases.

Special control outputs

The control output at PV alarm and control output at READY can be set.

• When the control method is other than the ON/OFF control (CtrL ≠ 0) and the

Heat/Cool control is set enabled (C26 = 1), [Output at READY (cool): C18] can
be displayed and set.

• The PV alarm status means that AL01, 02, or 03 occurs.

5-12

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Setting display/bank)

Display

Contents

Initial value

User level

Control action
(direct/reverse)
(Setup setting/Setup bank)

0: Heat control (Reverse)
1: Cool control (Direct)

0

Simple,
Standard,
High function

Heat/Cool control
(Setup setting/Setup bank)

0

Simple,
Standard,
High function

0: Disabled.
1: Enabled.

Item (Setting display/bank)

Display

Contents

Initial value

User level

Output operation at PV
alarm
(Setup setting/Setup bank)

0: Control calculation is continued.
1: Output at PV alarm is output.

0

High function

Output at PV alarm
(Setup setting/Setup bank)

0.0%

High function

-10.0 to +110.0%

Output at READY (Heat)
(Setup setting/Setup bank)

0.0%

Standard,
High function

-10.0 to +110.0%

Output at READY (Cool)
(Setup setting/Setup bank)

0.0%

Standard,
High function

-10.0 to +110.0%