6-10

Chapter 6. LIST OF DISPLAYS AND SETTING DATA

Display

Item

Contents

Initial
value

User
level

Remarks

Control output 1
range

1: 4 to 20mA
2: 0 to 20mA

1

0

Displayed when control
output 1 of the model is the
current output.
The decimal point position of
the scaling low limit/high limit
becomes 1 digit after the
decimal point when the
control output 1 type is
related to the MV and CT.
When the control output 1
type is related to the PV and
SP, the decimal point
position becomes the same
as that of the PV.

Control output 1 type

0: MV
1: Heat MV (for heat/cool control)
2: Cool MV (for heat/cool control)
3: PV
4: PV before ratio, bias, and filter
5: SP
6: Deviation
7: CT1 current value
8: CT2 current value
9: MFB (Invalid on SDC15)
10: SP+MV
11: PV+MV

0

0

Control output 1
scaling low limit

-1999 to +9999
The decimal point position may vary
depending on control output 1 type
(C43).

0

0

Control output 2
range

1: 4 to 20mA
2: 0 to 20mA

1

0

Control output 2 type

0: MV
1: Heat MV (for heat/cool control)
2: Cool MV (for heat/cool control)
3: PV
4: PV before ratio, bias, and filter
5: SP
6: Deviation
7: CT1 current value
8: CT2 current value
9: MFB (Invalid on SDC15)

3

0

Control output 2
scaling low limit

-1999 to +9999
The decimal point position may vary
depending on control output 2 type
(C48).

0

0

Displayed when control
output 2 of the model is the
current output.
The decimal point position of
the scaling low limit/high limit
becomes 1 digit after the
decimal point when the
control output 2 type is
related to the MV and CT.
When the control output 2
type is related to the PV and
SP, the decimal point
position becomes the same
as that of the PV.

Control output 2
scaling high limit

1000

0

Control output 1
scaling high limit

100.0

0

Control output 1 MV
scaling

200.0

0

0 to 9999
The decimal point position and unit
are same as for PV.

If the controller model uses
current output for control
output 1 and if the control
output 1 type is SP+MV or
PV+MV, this setting is
displayed.

Control output 2 MV
scaling

200.0

0

0 to 9999
The decimal point position and unit
are same as for PV.

If the controller model uses
current output for control
output 2 and if the control
output 2 type is SP+MV or
PV+MV, this setting is
displayed.

Handling Precautions

• If ROM version 1 of the instrument information bank(

Id02

) is prior to

2.04, SP+MV and PV+MV cannot be set in [Control output 1 type],
[Control output 2 type], and [Auxiliary output type ].

• If ROM version 1 of the instrument information bank(

Id02

) is prior to

2.04, SP+MV and PV+MV cannot be set in [Control output 1 MV
scaling], [Control output 2 MV scaling], and [Auxiliary output MV
scaling ].