Event channel def.

When the operation type is the timer start/stop, a target Event channel can be set.

• When the operation type of the same internal contact No. is set at “Timer

stop/start”, the display and setting can be made.

Input bit function

Four kinds of input bit functions are provided. What function of four functions is
used or is not used can be set.

• When the set value is “0”, the input bit function is not used and the default input

is used. The following shows the default input of each internal contact:

Internal Contact 1: DI (digital input) 1
Internal Contact 2: DI (digital input) 2
Internal Contact 3: OFF status

• In the input bit function, the logical operations (AND, OR) of each of internal

contacts 1 to 3 are combined. In input bit functions 1 to 4, the combination of the
logical operations may vary. The following shows one logical operation:

Logical AND

Logical OR

OFF and OFF = OFF

OFF or OFF = OFF

ON and OFF = OFF

ON or OFF = ON

ON and ON = ON

ON or ON = ON

• “OFF” is “contact open (OPEN)” or “0” when expressed using the numerical

value.

• “ON” is “contact close (CLOSE)” or “1” when expressed using the numerical

value.

5-34

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Setting display/bank)

Display

Contents

Initial value

User level

Internal Contact 1 Event
channel def.
(Setup setting/DI
Assignment bank)

0: Every Internal Event
1 to 5: Internal Event number

0

High function

0

Internal Contact 2 Event
channel def.
(Setup setting/DI
Assignment bank)

0

Internal Contact 3 Event
channel def.
(Setup setting/DI
Assignment bank)

Item (Setting display/bank)

Display

Contents

Initial value

User level

Internal Contact 1 Input bit
function
(Setup setting/DI
Assignment bank)

0: Not used (Default input)
1: Function 1 ((A and B) or (C and D))
2: Function 2 ((A or B) and (C or D))
3: Function 3 (A or B or C or D)
4: Function 4 (A and B and C and D)

0

High function

0

Internal Contact 2 Input bit
function
(Setup setting/DI
Assignment bank)

0

Internal Contact 3 Input bit
function
(Setup setting/DI
Assignment bank)