Nor-Cal SDC15 Controller User Manual

Page 204

Advertising
background image

CT (Current Transformer) input calibration

(1) Select the

[CT input calibration]

tab.

(2) Select a desired channel to be calibrated.

(3) Select

[Zero]

from the zero span selection items.

(When selecting a channel, perform the [

Zero]

calibration first, and then

perform the

[Span]

calibration next since “Zero/Span” is set for one channel.)

(4) Click

[Read]

.

(5) A current value of “0” is applied to the CT input terminal of the channel you

have selected and keep the apply status for approximately 30 sec. For details

about how to connect measuring instruments in the apply status, refer to the

following Figures:

(6) Click

[Write]

.

(7) Select

[Span]

from the zero span selection items.

(8) Click

[Read

].

(9) Apply a span current value to the CT input terminal of the channel you have

selected and keep the apply status for approximately 30 sec.

(10) Click

[Write]

.

(11) If any channels to be calibrated remain, return to operation step (2).

Handling Precautions

To calibrate the CT input, connect the DC current (mA) to the input

terminal.

11-4

Chapter 11. CALIBRATION

Current

generator

CT input 1

This unit

-

+

(13)

(14)

(15)

Current

generator

CT input 2

This unit

-

+

(13)

(14)

(15)