Cautions before starting the calibration

When calibrating the unit, strictly observe the following cautions. Failure to do so

may cause faulty accuracy:

• Before starting the calibration, supply the power to this unit for at least 1 hr.

• The ambient temperature of the calibration place must conform the standard

conditions specified in the unit specifications.

• Do not calibrate the unit in a place where it is in contact with the wind or the

ambient temperature fluctuates.

• Do not calibrate the unit with the measuring instruments having lower

specifications stated in the next section, ■

Measuring instruments required for

calibration

.

Measuring instruments required for calibration

Calibration procedures

I/O check

(1) Select the

[I/O Check]

tab.

(2) Select a desired item from the check contents.

(3) Click

[Execute]

.

The input system (key and digital input) is shown on the personal computer screen

while the input status (ON/OFF) of this unit is being read continuously.

For the output system (control output and event output), the status (ON/OFF) you

have checked on desired check boxes is output from the output terminal of this

unit.

PV input calibration

(1) Select the

[PV Calibration]

tab.

(2) Select the gain No. in the ascending order and perform the operation from step

(3).

(3) Click

[Read]

.

(4) Apply the voltage, current, and resistance values written next to the gain No. to

the PV input terminal.

For details about how to connect measuring instruments in the apply status, refer

11-2

Chapter 11. CALIBRATION

Measuring instrument

Specifications

Reference current/

Accuracy: ±0.1% or less, Minimum resolution: 100 µV

voltage generator

or less (voltage), Minimum resolution: 100 µA or less
(current)

Resistor

Accuracy: ±0.1% or less, Minimum resolution: 0.1

or

less

Ammeter

Accuracy: ±0.1% or less, Minimum resolution: 1µA or
less

Thermometer

Accuracy: ±0.1˚C or less, Minimum resolution: 0.1˚C or
less