Operation – Nor-Cal SDC15 Controller User Manual

Page 89

Advertising
background image

5-39

Operation

According to the operation type, direct/reverse, main setting, sub setting,
hysteresis, and other settings, the operation of the internal event becomes as
follows:

[List of internal event operations]

Note

For details about U (unit), refer to the attached glossary.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Operation type

Set value

Direct action

Reverse action

of operation

type

No event

0

Always OFF

Always OFF

PV high limit

1

PV low limit

2

PV high/low limit

3

Deviation high

4

limit

Deviation low limit

5

Deviation high/

6

low limit

Deviation high limit

7

(Final SP reference)

Deviation low limit

8

(Final SP reference)

Deviation high/

9

low limit

(Final SP reference)

ON

HYS

ON

HYS

Main setting

Main setting

PV

PV

Main setting

PV

Main setting

PV

ON

HYS

ON

HYS

Main setting Sub-setting

PV

SP

ON

HYS

ON

HYS

ON

HYS

HYS

Main setting Sub-setting

PV

SP

Main setting

Sub-setting

Main setting Sub-setting

PV

PV

ON

HYS

ON

HYS

ON

HYS

HYS

ON

HYS

ON

HYS

SP + Main setting

SP + Main setting

PV

PV

SP + Main setting

PV

SP + Main setting

PV

ON

HYS

ON

HYS

Same as the direct action of the deviation high
limit when the SP ramp is not used. The
difference is that the SP ramp does not use the
current SP, but it uses the final SP.

Same as the reverse action of the deviation
high limit when the SP ramp is not used. The
difference is that the SP ramp does not use the
current SP, but it uses the final SP.

Same as the direct action of the deviation low
limit when the SP ramp is not used. The
difference is that the SP ramp does not use the
current SP, but it uses the final SP.

Same as the reverse action of the deviation
low limit when the SP ramp is not used. The
difference is that the SP ramp does not use the
current SP, but it uses the final SP.

Same as the direct action of the deviation
high/low limit when the SP ramp is not used.
The difference is that the SP ramp does not
use the current SP, but it uses the final SP.

Same as the reverse action of the deviation
high/low limit when the SP ramp is not used.
The difference is that the SP ramp does not
use the current SP, but it uses the final SP.

shows that the ON/OFF is changed at this value.

shows that the ON/OFF is changed at a point that
"1U" is added to this value.

shows that the ON/OFF is changed at this value.

shows that the ON/OFF is changed at a point that
"1U" is added to this value.