Ct type, Ct output, Ct measurement wait time – Nor-Cal SDC15 Controller User Manual

Page 120

Advertising
background image

5-70

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

CT type

A desired operation type can be set for each of CT input 1 or CT input 2.

• When the optional model has two CT input points, the display and setting can be

made.

• When the CT type is set at “current value measurement”, the current value at

output ON is updated regardless of the output ON/OFF status and the current
value at output OFF is fixed at “0.0A”.

CT output

When the CT type is set at “heater burnout detection”, the output of the output
ON/OFF monitor object can be set.

• When the optional model has two CT input points and the CT type is set at

“heater burnout detection”, the display and setting can be made.

CT measurement wait time

When the CT type is set at “heater burnout detection”, a period of time between
changing of the output ON/OFF and starting of the current value measurement can
be set.

• When the optional model has two CT input points and the CT type is set at

“heater burnout detection”, the display and setting can be made.

• When the measurement wait time has elapsed after the ON/OFF status of the

output to be monitored has been changed, the measurement of the current value
is started. When 100 ms have elapsed after that, the measurement of the current
value is completed.

Item (Setting display/bank)

Display

Contents

Initial value

User level

CT1 operation type
(Setup setting/Setup bank)

0: Heater burnout detection
1: Current value measurement

0

Simple,
Standard,
High function

CT2 operation type
(Setup setting/Setup bank)

0

Item (Setting display/bank)

Display

Contents

Initial value

User level

CT1 output
(Setup setting/Setup bank)

0: Control output 1
1: Control output 2
2: Event output 1
3: Event output 2
4: Event output 3

0

Simple,
Standard,
High function

CT2 output
(Setup setting/Setup bank)

0

Item (Setting display/bank)

Display

Contents

Initial value

User level

CT1 measurement wait time
(Setup setting/Setup bank)

20 to 300 ms

30ms

Simple,
Standard,
High function

CT2 measurement wait time
(Setup setting/Setup bank)

30ms

Advertising