Manual mode change, On/off control – Nor-Cal SDC15 Controller User Manual

Page 63

Advertising
background image

5-13

MANUAL mode change

The control output when the AUTO mode is changed to the MANUAL mode can
be set.

• When [Output operation at changing Auto/Manual: C19] is set at [0: Bumpless

transfer], the manipulated variable (MV) when the AUTO mode is changed to
the MANUAL mode is retained. When set at [1: Preset], the manipulated
variable (MV) is set to [Preset MANUAL value: C20] when the AUTO mode is
changed to the MANUAL mode.

• When the control method is other than ON/OFF control (CtrL ≠ 0), [Output

operation at changing Auto/Manual: C19] and [Preset MANUAL value: C20]
can be displayed and set.

• When the Heat/Cool control is not used (C26 = 0), the initial value of [Preset

MANUAL value: C20] is [0.0]. On the contrary, when the Heat/Cool control is
used (C26 =1), this initial value becomes [50.0].

Handling Precautions

When the unit is in the MANUAL mode if the power is turned ON, the

set value of C20 becomes the manipulated variable (MV).

ON/OFF control

The ON/OFF control related items can be set.

• [Differential (for ON/OFF control): dIFF] and [ON/OFF control action point

offset: oFFS] can be displayed and set when the control method is the ON/OFF
control (CtrL = 0).

• The following Figure shows the operation of the ON/OFF control:

● shows that the ON/OFF is changed at this value.
❍ shows that the ON/OFF is changed at a point that "1U" is added to this value.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Setting display/bank)

Display

Contents

Initial value

User level

Output operation at
changing Auto/Manual
(Setup setting/Setup bank)

0: Bumpless transfer
1: Preset

0

Standard,
High function

Preset MANUAL value
(Setup setting/Setup bank)

0.0 or 50.0%

Standard,
High function

-10.0 to +110.0%

Item (Setting display/bank)

Display

Contents

Initial value

User level

Differential (for ON/OFF
control) (Parameter
setup/Parameter bank)

0 to 9999U

5U

Simple,
Standard,
High function

ON/OFF control action
point offset (Parameter
setup/Parameter bank)

0U

High function

-1999 to +9999U

SP + oFFS

Heat control (Reverse action)

Cool control (Direction action)

PV

ON

dIFF

SP + oFFS

PV

ON

dIFF