Chapter 5. detailed description of each function – Nor-Cal SDC15 Controller User Manual

Page 92

Advertising
background image

5-42

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Operation type

Set value

Direct action

Reverse action

of operation

type

Loop diagnosis 2

21

PV to be used

as reference

Main setting

Time

Conditions 3

ON delay

set time

ON delay is started when conditions 1 and 2 are satisfied.

Area satisfying

conditions 1

Sub-setting

(0 or more)

Area satisfying

conditions 2

Time

Time

PV

MV

EV

ON

HYS

Main setting

Time

Conditions 3

ON delay

set time

ON delay is started when conditions 1 and 2 are satisfied.

Area satisfying

conditions 1

Area satisfying

conditions 2

Time

Time

PV

MV

EV

ON

HYS

Sub-setting

(0 or more)

PV to be used

as reference

The event is turned ON when any change in PV corresponding to increase/decrease in MV
(Manipulated variable) is not observed.
This event is used to detect any fault at the operation end.

Setting items
• Main setting: MV (Manipulated variable)
• Sub-setting: Change in PV from the point that the MV exceeds the main setting.
• ON delay time: Diagnosis time

Operation specifications
The event is turned ON when the MV exceeding the main setting is held (conditions 2) and
the PV does not reach the value that the sub-setting is added to (subtracted from) the PV at
the point that the MV exceeds the main setting within the diagnosis time (ON delay time)
(conditions 1).

CAUTION
When setting the ON delay, it is necessary to put in "High function configuration".
The default setting of the ON delay before shipment is 0.0s.

Heat control

Cool control