Operation in case of pv input failure, Refer to – Nor-Cal SDC15 Controller User Manual

Page 200

Advertising
background image

Operation in case of PV input failure

(1) AL01, 02, or 03 occurs.

Control output: It is possible to make the settings so that the operation is

continued or not continued.

Other operation: Operation is continued.

(2) AL occurs in cases other than those shown above.

All operations are continued.

The following Table shows the indications and alarms of this unit by the sensor

type if PV input failure occurs:

Thermocouple

RTD

DC voltage/DC current

10-2

Chapter 10. MAINTENANCE AND TROUBLESHOOTING

Failure status

Range No.

Indication value

Alarm code

Burnout

84 (0 to 1V)

Downscale (-3%FS)

AL02

86 (1 to 5V)

Downscale (-10%FS)

AL02

87 (0 to 5V)

Downscale (-3%FS)

AL02

88 (0 to 10V)

Downscale (0%FS)

None

89 (0 to 20mA)

Unknown (around 0%FS)

None

90 (4 to 20mA)

Downscale (-10%FS)

AL02

Failure status

Range No.

Indication value

Alarm code

Sensor burnout

Upscale (110%FS)

AL01

CJ failure

PV having incorrect cold

AL03

contact compensation

Over-range, burnout

19 (PLII)

1365˚C (105%FS)

AL01

Failure status

Range No.

Indication value

Alarm code

RTD burnout

Upscale (110%FS)

AL01

A-wire burnout

Upscale (110%FS)

AL01

B-wire burnout

Upscale (110%FS)

AL01, AL03

C-wire burnout

Upscale (110%FS)

AL01, AL03

2- or 3-wire burnout

Upscale (110%FS)

AL01, AL03

A- and B-wire short-circuit

Downscale (-10%FS)

AL02

A- and C-wire short-circuit

Downscale (-10%FS)

AL02

A- and B-wire/A- and

41 (Pt100)

-235˚C (-5%FS)

AL02

C-wire short-circuit

A- and B-wire/A- and

42 (JPt100)

-235˚C (-5%FS)

AL02

C-wire short-circuit