Nor-Cal SDC15 Controller User Manual

Page 112

Advertising
background image

• DI Assignment

Note. The internal DI No. is indicated at the mark of "x" shown in the Display

column.

Setting points

The timer startup conditions are set to logical AND of DI1 and temperature
attainment (Internal Event 2: Deviation high limit).
The mode (RUN/READY) selection is used as conditions for logical AND of the
A contact of DI1 and the B contact of the timer. However, since the mode is the
READY mode when the contact is ON, it is reversed in the final stage of internal
contact 2.

DI Assignment (Internal Contact 1): Input/Output port setup

5-62

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

DI Assignment

Display

Internal Contact 1

Internal Contact 2

Operation type

DIx.1

17: Timer stop/start

7: RUN/READY

Input bit function

DIx.2

1: Function 1 (A and B) or

1: Function 1 (A and B) or

(C and D)

(C and D)

Input assign A

DIx.3

2: DI1

2: DI1

Input assign B

DIx.4

11: Internal Event 2

10: Internal Event 1

(Setting = 4: Deviation

(Setting = 32: Timer

high limit)

(Status))

Input assign C

DIx.5

0: Normally opened.

0: Normally opened.

(Normally Off = 0)

(Normally Off = 0)

Input assign D

DIx.6

0: Normally opened.

0: Normally opened.

(Normally Off = 0)

(Normally Off = 0)

Polarity A

DIx.7

0: Direct

0: Direct

Polarity B

DIx.7

0: Direct

1: Reverse

Polarity C

DIx.7

0: Direct

0: Direct

Polarity D

DIx.7

0: Direct

0: Direct

Polarity

DIx.8

0: Direct

1: Reverse

Event channel def.

DIx.9

1

----

Logical AND of DI1 and deviation high limit event

Timer start-up contact

Advertising