Fixed length continuous data read command (RD command)

This command reads continuous data in two-byte units. This command is suitable

for handling data in ladder programs sent by PLC communications as the data is of

a fixed length.

The start data address is expressed as four hexadecimal digits. The data count is

expressed as four digits, and data is expressed as four X n (n is a positive integer)

hexadecimal digits.

Send message

The read start data address (four hexadecimal digits) and the read data count (four

hexadecimal digits) are sent.

Response message

If the message is sent successfully, the termination code is taken to be normal (two

decimal digits) and returned appended with the read data count (four hexadecimal

digits X read data count) specified by the command. If message transmission ends

in error, the termination code is taken to be in error (two decimal digits) and

returned without the read data appended.

Maximum read data count per message

Up to 28 words for both RAM and EEPROM areas

7-8

Chapter 7. CPL COMMUNICATIONS FUNCTIONS

(1) Fixed length continuous data read command
(2) Start data word address
(3) Data count

R

(1)

D

(2)

(3)

0

• Normal termination (reading of single data item)

(1)

0

• Normal termination (reading of multiple data items)

0

(1)

0

(2)

(3)

(4)

• Abnormal termination

X

(1)

X

The abnormal termination code is entered at XX.
For details of codes,
refer to

7-6, List of Termination Codes (on page 7-14).

(2)

(1) Termination code
(2) Data
(3) Data 2 to (n-1)
(4) Data (n)