In the Heat/Cool control, the AT function is run in the status that both the heat MV
and cool MV are operated.

In the first half, the MV is changed to the MV low limit/MV high limit. In the
latter half, the MV is changed in a slightly narrow range.

The following Figure shows an example of the AT execution when the Heat/Cool
control dead zone is 0.0%, Heat/Cool control change point is 50.0%, MV low limit
is 0.0%, and MV high limit is 100.0%:

Handling Precautions

• Before starting the AT function, put the PV input and/or operation end

(heater power, etc.) in the controllable status.

• When the control method is set at “ON/OFF control” ([CtrL] = 0), the

AT function cannot be started. To operate the AT function, set the
control method to “Fixed PID” ([CtrL] = 1) or “ST” ([CtrL] = 2).

• To start the AT, it is absolutely necessary that the operation is in the

READY mode and AUTO mode, and no PV input errors occur.

• If the mode is changed to the READY mode or MANUAL mode or if

the PV input error or power failure occurs during execution of the AT
function, the AT function is stopped without changing of the PID
constants.