• When using the Heat/Cool control (C26 = 1), the display and setting can be

made.

• When MV ≥ 50%, the control is changed to the PID (heat).

• When MV < 50%, the control is changed to the PID (cool).

• When the heat/cool change is set at “energy saving” (C27 = 1), the heat/cool

change is suppressed to indirectly obtain the energy saving effect. However,
when the heat/cool dead zone (C28) is less than 0.0%, the energy saving effect
cannot be obtained.

• How the relationship between the output (heat) and output (cool) is made for the

PID control result (MV) is set.

Constants oL and oH function as shown in the Figure below.

5-16

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

100.0%

0.0%

Heat MV

100.0%

Cool MV

0.0%

0.0%

50.0%

100.0% MV

100.0%

0.0%

Heat MV

100.0%

Cool MV

0.0%

0.0%

50.0%

Dead zone

Dead zone > 0.0%

Dead zone = 0.0%

100.0% MV

100.0%

0.0%

Heat MV

100.0%

Cool MV

0.0%

0.0%

50.0%

Absolute value of

dead zone

Dead zone < 0.0%

100.0% MV

100%

100%

0%

Cool

MV

Heat

MV

MV

oH

(cool)

oL

(cool)

oL

(heat)

oH

(heat)