Item name

RAM address

EEPROM address

RAM

EEPROM

Decimal point

Remarks

Decimal Hexadecimal Decimal Hexadecimal Read Write Read Write information

Operation

LSP group selection

9103

238F

25487

638F

Same as RAM address

display

14592 (decimal). Writing is

enabled under no DI

Assignment conditions.

(Note 3)

(Reserved for future extension.)

9104

2390

25488

6390

X

X

MV (Manipulated Variable)

9105

2391

25489

6391

1

Same as RAM address

14594 (decimal). Writing is

enabled in the MANUAL

mode.

Heat MV (Manipulated Variable)

9106

2392

25490

6392

X

X

1

Same as RAM address

14420 (decimal).

Cool MV (Manipulated Variable)

9107

2393

25491

6393

X

X

1

Same as RAM address

14421 (decimal).

(Reserved for future extension.)

9108

2394

25492

6394

X

X

1

Same as RAM address

14417 (decimal).

AT progress

9109

2395

25493

6395

X

X

CT (Current transformer)

9110

2396

25494

6396

X

X

1

Same as RAM address

current value 1

14418 (decimal).

CT (Current transformer)

9111

2397

25495

6397

X

X

1

Same as RAM address

current value 2

14419 (decimal).

Timer remain time 1

9112

2398

25496

6398

X

X

S

Timer remain time 2

9113

2399

25497

6399

X

X

S

Timer remain time 3

9114

239A

25498

639A

X

X

S

Timer remain time 4

9115

239B

25499

639B

X

X

S

Timer remain time 5

9116

239C

25500

639C

X

X

S

(Reserved for future extension.)

9117

239D

25501

639D

X

X

S

(Reserved for future extension.)

9118

239E

25502

639E

X

X

S

(Reserved for future extension.)

9119

239F

25503

639F

X

X

S

(Reserved for future extension.)

9120

23A0

25504

63A0

X

X

S

(Reserved for future extension.)

9121

23A1

25505

63A1

X

X

S

(Reserved for future extension.)

9122

23A2

25506

63A2

X

X

S

LSP value in use

9123

23A3

25507

63A3

P

Same as RAM address

14593 (decimal). (Note 2)

PV before ratio, bias, and filter

9124

23A4

25508

63A4

X

X

P

(Reserved for future extension.)

9125

23A5

25509

63A5

X

X

P

Status

Input alarm status

9201

23F1

25585

63F1

X

X

Bit 0: AL01 (PV over-range)

Bit 1: AL01 (PV under-

range)

Bit 2: AL03 (CJ, RTD

burnout)

Bits 3 to 15: Undefined.

Instrument alarm status

9202

23F2

25586

63F2

X

X

Bits 0 to 1: Undefined.

Bit 2: AL70 (A/D)

Bit 3: AL95 (Set data)

Bit 4: AL96 (Adjustment

data)

Bit 5: AL97 (Set data/RAM)

Bit 6: AL98 (Adjustment

data/RAM)

Bit 7: AL99 (ROM)

Bits 8 to 15 Undefined.

9-9

Chapter 9. LIST OF COMMUNICATION DATA

(Note 2) If the value is read immediately after it has been written into the SP or the LSP in use, the value still may

not be changed. The value is updated after the cycle time has elapsed.

(Note 3) If the SP or the LSP in use is read immediately after the value has been written into the LSP group

selection, the value still may not be changed. The value is updated after the cycle time has elapsed.

Advertising