Terminal assignment label symbols, Wiring precautions – Nor-Cal SDC15 Controller User Manual

Page 40

Advertising
background image

4-2

Terminal assignment label symbols

The following table shows the meanings of the symbols used for the terminal
assignment label attached to the side panel of this unit:

Wiring Precautions

• Before starting the wiring work, carefully check the label on the side panel of this

unit to understand the model No. and terminal No. to carry out the wiring

properly.

• For panel mount type, use an appropriate crimp type terminal lug suitable for the

M3 screw to connect the terminals. The tightening torque of the terminal screw
must be 0.4 to 0.6N·m.

• For socket mount type, use an appropriate crimp type terminal lug suitable for

the M3.5 screw to connect the terminals. The tightening torque of the terminal
screw must be 0.78 to 0.98 N·m or less.

• Pay special attention so that no crimp terminals are in contact with adjacent

terminals.

• Keep the input/output signal cables 50cm or more away from the drive power

cable and/or power cable. Additionally, do not pass the input/output signal
cables and the drive power cable and/or power cable together through the same
conduit or duct.

• When connecting this unit and other measuring instrument in parallel, carefully

check the conditions necessary for other instrument before starting the
instrumentation.

• The digital input is so designed that it is non-voltage input. A contact for micro

current must be used.

• Pass the conductor, to which the heater current flows, through the current

transformer. Additionally, carefully check that the heater current does not
exceed the allowable current level stated in the specification. If the heater
current exceeds the allowable current level, this might cause damage to this unit.

• The input of the current transformer cannot be used for the phase angle control.

• For panel mounting type

(C15T)

, an optional terminal cover is available to

prevent electric shock. (Model No.: 81446898-001)

• The part between the control output 1 and control output 2 is not isolated. When

necessary, use an appropriate isolator.

• Do not connect any terminating resistor to both ends of the RS-485

communication path. Doing so might cause the communication to fail.

• Devices and systems to be connected to this unit must have the basic insulation

suitable for the maximum operating voltage levels of the power supply and
input/output part.

Chapter 4. WIRING

Symbol

Contents

DC

~

AC

Caution, Electric shock hazard

Caution

Concave part of

main body case

Terminal cover