Chapter 6. LIST OF DISPLAYS AND SETTING DATA

Display

Item

Contents

Initial
value

User
level

Remarks

Output operation at
changing Auto/Manual

0: Bumpless transfer
1: Preset

0

1

Displayed when the control
method is other than the
ON/OFF control (CtrL≠0).
When the operation mode is
the MANUAL mode at power
ON, the preset MANUAL
value (C20) becomes the
Manipulated Variable (MV).

Preset MANUAL
value

-10.0 to +110.0%

0.0 or

50.0

1

Initial output type
(mode) of PID control

0: Auto
1: Not initialized.
2: Initialized (If SP value different

from the current value is input.)

0

2

Initial output of PID
control

-10.0 to +110.0%

0.0 or

50.0

2

Heat/Cool control

0: Not used.
1: Used.

0

0

Displayed when the control
method is other than the
ON/OFF control (CtrL≠0).
When set at “1”, the control
action is set to the reverse
action (C14 = 0), the preset
MANUAL value (C20) is set
to “50.0”, and the initial
output of the PID control
(C22) is changed to “50.0”.

Heat/Cool selection

0: Normal
1: Energy saving

0

1

Heat/Cool control
dead zone

-100.0 to +100.0%

0.0

0

Heat/Cool control
change point

-10.0 to +110.0%

50.0

2

LSP system group

1 to 4

1

0

SP ramp unit

0: 0.1U/s
1: 0.1U/min
2: 0.1U/h

1

2

"0.1U" shows that the
decimal point position of the
PV is shifted one digit
rightward.

Displayed when the
Heat/Cool control is used
(C26 = 1).

CT1 operation type

0: Heater burnout detection
1: Current value measurement

0

0

Displayed when the optional
model has two current
transformer input points.

CT1 output

0: Control output 1
1: Control output 2
2: Event output 1
3: Event output 2
4: Event output 3

0

0

Displayed when the optional
model has two current
transformer input points and
the CT1 operation type is set
at "heater burnout detection"
(C36 = 0).

CT1 measurement
wait time

30 to 300ms

30

0

CT2 operation type

Same as CT1

0

0

Displayed when the optional
model has two current
transformer input points.

CT2 output

Same as CT1

0

0

Displayed when the optional
model has two current
transformer input points and
the CT2 operation type is set
at "heater burnout detection"
(C39 = 0).

CT2 measurement
wait time

Same as CT1

30

0