Operation type – Nor-Cal SDC15 Controller User Manual

Page 83

Advertising
background image

5-33

Operation type

The operation type by the internal contact function can be set.

Handling Precautions

• For [1 to 3: LSP group selection], the value that “1” is added to the

sum of weights (+ 1, + 2, +4), the internal contact of which is turned
ON, becomes the LSP group number.

• Do not use [14: PV value hold], [15: PV Max. hold], and [16: PV Min.

hold] with they mixed.

• Do not set the same operation type other than [0: No function] and [1

to 3: LSP group selection] for multiple internal contacts.

• When using the Heat/Cool control, do not use [12: Control action

direct/reverse selection].

• For timer stop/start, set a target Event channel using [Event channel

def. of internal contact].

The following Table shows the contents of the dI settings:

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Setting display/bank)

Display

Contents

Initial value

User level

Internal Contact 1
Operation type (Setup
setting/DI Assignment bank)

0 to 20
For details about function by each set value,
refer to the Table below.

0

Simple,
Standard,
High function

0

Internal Contact 2
Operation type (Setup
setting/DI Assignment bank)

0

Internal Contact 3 Operation
type (Setup setting/DI
Assignment bank)

Set value

Function

Operation at OFF

Operation at ON

0

No function

None

None

1

LSP group selection (0/+1)

LSP No.: +0

LSP No.: +1

2

LSP group selection (0/+2)

LSP No.: +0

LSP No.: +2

3

LSP group selection (0/+4)

Invalid

Invalid

4

PID group selection (0/+1)

Invalid

Invalid

5

PID group selection (0/+2)

Invalid

Invalid

6

PID group selection (0/+4)

Invalid

Invalid

7

RUN/READY mode selection

RUN

READY

8

AUTO/MANUAL mode selection

AUTO

MANUAL

9

LSP/RSP mode selection

Invalid

Invalid

10

AT (Auto tuning) Stop/Start

AT Stop

AT Start

11

ST (Self-tuning) disabled/enabled

ST disabled

ST enabled

12

Control action direct/reverse selection

Set action

Reverse action of setting

13

SP ramp enabled/disabled

SP ramp enabled

SP ramp disabled

14

PV value hold

No-hold

Hold

15

PV Max. hold

No-hold

Hold

16

PV Min. hold

No-hold

Hold

17

Timer Stop/Start

Timer stop

Timer start

18

Release all DO latches

Continue if latch exists.

Latch release

19

Advance operation

Invalid

Invalid

20

Step hold

Invalid

Invalid

Advertising