Nor-Cal SDC15 Controller User Manual

Page 94

Advertising
background image

5-44

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Operation type

Set value

Direct action

Reverse action

of operation

type

Alarm

23

ON if alarm occurs (alarm code AL01 to 99).

OFF if alarm occurs (alarm code AL01 to 99).

(status)

OFF in other cases.

ON in other cases.

READY

24

ON in the READY mode.

OFF in the READY mode.

(status)

OFF in the RUN mode.

ON in the RUN mode.

MANUAL

25

ON in the MANUAL mode.

OFF in the MANUAL mode.

(status)

OFF in the AUTO mode.

ON in the AUTO mode.

Invalid

26

Always OFF

Always ON

During AT

27

ON when AT is executed.

OFF when AT is executed.

(Status)

OFF when AT is stopped.

ON when AT is stopped.

During SP ramp

28

ON during SP ramp.

OFF during SP ramp.

OFF when SP ramp is not performed or is completed. ON when SP ramp is not performed or is completed.

Control action

29

ON during direct action (cooling).

OFF during direct action (cooling).

(status)

OFF during reverse action (heating).

ON during reverse action (heating).

ST setting standby

30

ON in the ST setting standby.

OFF in the ST setting standby.

(status)

OFF in the ST setting completion.

ON in the ST setting completion.

Invalid

31

Always OFF

Always ON

Timer

32

(status)

High and low limits

33

Invalid in this unit.

Invalid in this unit.

of MFB value

ON/OFF status is undetermined.

ON/OFF status is undetermined.

The direct and reverse action settings are disabled for the timer event.
When using the timer event, it is necessary to set the operation type of the DI assignment to
"Timer Start/Stop". Additionally, when setting the event channel designation of the DI
assignment, multiple timer events are controlled from individual internal contacts (DI).

Setting items
• ON delay time: A period of time necessary to change the event from OFF to ON after DI has

been changed from OFF to ON.

• OFF delay time: A period of time necessary to change the event from ON to OFF after DI

has been changed from ON to OFF.

Operation specifications
• The event is turned ON when DI ON continues for ON delay time or longer.
• The event is turned OFF when DI OFF continues for OFF delay time.
• In other cases, the current status is continued.

CAUTION
When setting the ON delay and OFF delay, it is necessary to put in "High function
configuration".
The default settings of the ON delay and OFF delay before shipment are 0.0s.
The default setting of the event channel designation of the DI assignment before shipment is
"0". In this case, the timer event start/stop can be set for all internal events from one internal
contact (DI).
Additionally, as one or more event channel designation is set, the timer event start/stop can
be set for one internal event specified by one internal contact (DI).
However, when setting the event channel of the DI assignment, it is necessary to put in "High
function configuration".

Time

ON

Internal event

ON

DI

OFF delay

ON delay