Output scaling low limit/high limit – Nor-Cal SDC15 Controller User Manual

Page 117

Advertising
background image

5-67

Output scaling low limit/high limit

The output scaling low limit and high limit of the current output can be set.

• When the object control output is the current output, the display and setting can

be made.

• The following Figures show the relationship between the numeric value and

output of the output type using the output scaling low limit/high limit settings:

However, the output is 0 to 110% in a range of 0 to 20mA.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Setting display/bank)

Display

Contents

Initial value

User level

Control output 1 scaling low
limit (Setup setting/Setup
bank)

-1999 to +9999
The decimal point position may vary so that it
meets the output type.

0.0

Simple,
Standard,
High function

Control output 1 scaling high
limit (Setup setting/Setup
bank)

100.0

Control output 2 scaling low
limit (Setup setting/Setup
bank)

0

Control output 2 scaling high
limit (Setup setting/Setup
bank)

1000

Output (%)

Output (%)

-10

0

100

110

-10

0

100

110

Input

Low limit

Low limit

Low limit < High limit

Low limit > High limit

High limit

High limit

Input