PV input range table (Thermocouple)

PV input range table (RTD)

*1: The accuracy of a B thermocouple is ±5%FS for a

range of 260˚C or less, ±1%FS for 260 to 800˚C.
The indicated low limit for a B thermocouple is 20˚C.
However, if ROM version 1 of the instrument
information bank (

Id02

) is prior to 2.04, the value is

-180˚C.

*2: PL II thermocouple is a range, which has been added

to the units manufactured from July, 2003.

PV input range table (DC voltage/DC current)

Handling Precautions

• When the C01 PV input range number is set, the decimal point position

and range are initially set automatically as shown in the tables. For

details on the decimal point, refer to the description of setup C04

(decimal point position) on page 5-4.

• For details about the accuracy of each PV range type, refer to;

Chapter 13, SPECIFICATIONS (on page 13-1).

5-2

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

C01

Sensor

Range

Range

C04

C04

C04 initial value

set value

type

(Celsius)

(Fahrenheit)

display

range

when C01 settings

1

K

-200 to +1200˚C -300 to + 2200˚F

----

(Not setting) (No decimal point)

2

K

0 to 1200˚C

0 to 2200˚F

----

(Not setting) (No decimal point)

3

K

0.0 to 800.0˚C

0 to 1500˚F

----

(Not setting) (No decimal point)

4

K

0.0 to 600.0˚C

0 to 1100˚F

----

(Not setting) (No decimal point)

5

K

0.0 to 400.0˚C

0 to 700˚F

----

(Not setting) (No decimal point)

6

K

-200.0 to +400.0˚C -300 to + 700˚F

----

(Not setting) (No decimal point)

7

K

-200.0 to +200.0˚C -300 to + 400˚F

----

(Not setting) (No decimal point)

9

J

0.0 to 800.0˚C

0 to 1500˚F

----

(Not setting) (No decimal point)

10

J

0.0 to 600.0˚C

0 to 1100˚F

----

(Not setting) (No decimal point)

11

J

-200.0 to +400.0˚C -300 to + 700˚F

----

(Not setting) (No decimal point)

13

E

0.0 to 600.0˚C

0 to 1100˚F

----

(Not setting) (No decimal point)

14

T

-200.0 to +400.0˚C -300 to + 700˚F

----

(Not setting) (No decimal point)

15

R

0 to 1600˚C

0 to 3000˚F

----

(Not setting) (No decimal point)

16

S

0 to 1600˚C

0 to 3000˚F

----

(Not setting) (No decimal point)

17

B

0 to 1800˚C

0 to 3300˚F

----

(Not setting) (No decimal point)

18

N

0 to 1300˚C

0 to 2300˚F

----

(Not setting) (No decimal point)

19

PL II

0 to 1300˚C

0 to 2300˚F

----

(Not setting) (No decimal point)

20

WRe5-26

0 to 1400˚C

0 to 2400˚F

----

(Not setting) (No decimal point)

21

WRe5-26

0 to 2300˚C

0 to 4200˚F

----

(Not setting) (No decimal point)

24

DIN U -200.0 to +400.0˚C -300 to + 700˚F

----

(Not setting) (No decimal point)

25

DIN L

-100.0 to +800.0˚C -150 to + 1500˚F

----

(Not setting) (No decimal point)

C01

Sensor type

Range (C05, C06)

C04

C04

C04 initial value

set value

display range when C01 settings

84

0 to 1V

• Scaling range is -1999 to +9999.

0 to 3

No change

86

1 to 5V

• When C01 is changed, the range (C05, C06)

0 to 3

No change

87

0 to 5V

default defaults to 0 to 1000.

0 to 3

No change

88

0 to 10V

0 to 3

No change

89

0 to 20mA

0 to 3

No change

90

4 to 20mA

0 to 3

No change

C01

Sensor

Range

Range

C04

C04

C04 initial value

set value

type

(Celsius)

(Fahrenheit)

display

range

when C01 settings

41

Pt100

-200.0 to +500.0˚C -300 to + 900˚F

----

(Not setting) (No decimal point)

42

JPt100 -200.0 to +500.0˚C -300 to + 900˚F

----

(Not setting) (No decimal point)

43

Pt100

-200.0 to +200.0˚C -300 to + 400˚F

----

(Not setting) (No decimal point)

44

JPt100 -200.0 to +200.0˚C -300 to + 400˚F

----

(Not setting) (No decimal point)

45

Pt100

-100.0 to +300.0˚C -150 to + 500˚F

----

(Not setting) (No decimal point)

46

JPt100 -100.0 to +300.0˚C -150 to + 500˚F

----

(Not setting) (No decimal point)

51

Pt100

-50.0 to +200.0˚C

-50 to + 400˚F

0 to 1

1

52

JPt100

-50.0 to +200.0˚C

-50 to + 400˚F

0 to 1

1

53

Pt100

-50.0 to +100.0˚C

-50 to + 200˚F

0 to 1

1

54

JPt100

-50.0 to +100.0˚C

-50 to + 200˚F

0 to 1

1

63

Pt100

0.0 to 200.0˚C

0 to + 400˚F

0 to 1

1

64

JPt100

0.0 to 200.0˚C

0 to + 400˚F

0 to 1

1

67

Pt100

0.0 to 500.0˚C

0 to + 900˚F

----

(Not setting) (No decimal point)

68

JPt100

0.0 to 500.0˚C

0 to + 900˚F

----

(Not setting) (No decimal point)

Advertising