6 ring-coupling port, 7 ring-coupling redundancy-mode, Ring-coupling port – Pilz PSSnet SHL 8T MRP User Manual

Page 305

Advertising
background image

CLI Commands: Switching

PSSnet SHL - Command Line Interface

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany

5.5 Redundant Coupling

305

5.5.6 ring-coupling port

Configure the Ring Coupling's ports. Possible values are:

D

control Enter the Ring Coupling's control coupling port in outband

configurations.

D

local Enter the Ring Coupling's local coupling port.

D

partner Enter the Ring Coupling's partner coupling port in single mode

configuration.

Default

none

Format

ring-coupling port <{control|local|partner}> <slot/
port>

Mode

Global Config

5.5.7 ring-coupling redundancy-mode

Configure the Ring Coupling's redundancy mode. Possible values are:

D

extended Slave responds to a failure in the remote ring or network.

D

normal Slave does not respond to a failure in the remote ring or network.

Default

extended

Format

ring-coupling redundancy-mode <{extended|normal}>

Mode

Global Config

Advertising