Section

4

Start-Up & Troubleshooting

4-3

Zone Manager Communications

The Zone Manager is the main communication device on the Basic System. It must be
wired correctly and connected to 24VAC power for the system to function. The Zone
Manager must also be addressed correctly. The Zone Manager is normally addressed as
address 0 but should be addressed as 17 if a CommLink is used. Always be sure to
double-check all communication wiring and addressing before initial commissioning of
the system. The address switch must be set and the power cycled in order for the address
to be recognized by the system. Please see Figure 4-2 for the Basic Zone Manager
addressing information.

Figure 4-2: Zone Manager Communications Wiring & Address Switch Setting

U13

CX13

EPROM

U11

CX11

U10

RAM

CX10

JO2

32K

8K

16

32

2

8

4

ADD

1

NET

B

V9

V8

V7

R

FAN

COOL1

COOL2

HEAT1

HEAT2

K8

K7

K6

K5

K4

K3

CLOSE

OPEN

GND

FDBK

V4

V3

V6

V5

TB7

R57

HEAT2

D31

HEAT1

D22

R56

D21

R52

COOL2

COOL1

R46

D20

FAN

D19

R44

CLOSE

D18

R43

D23

D24

D26

D25

D29

D30

D28

D27

SW1

U14

CX14

MADE IN U.S.A.

1992

RN2

1

R58

U15

CX15

R59

R60

RS-485

COMM DRIVER

T

SH

R

U12

CX12

R49

R55

R45

R47

R48

C22

COMM

P1

CX9

U9

TB8

RN1

BYPASSPDAMPER

RS-485

Communications

To CommLink

When Used

Address Switch Must Be Set

To Address 0 on Zone Manager Board

As Shown

Address Switch Must Be Set

To Address 17 on Zone Manager

Board When CommLink Is Used

Zone Manager
Address Switch

Zone Manager
Address Switch

These Switches Must Be
In The OFF Position
As Shown

These Switches Must Be
In The OFF Position
As Shown

ADD

ADD

1

1

2

2

4

4

8

8

16

16

32

32

B

B

NET

NET

ADD

ADD

32

32

B

B

NET

NET

16

16

8

8

4

4

1

1

2

2

OFF

>

OFF

>

RockerDown

RockerDown

Basic System Without CommLink

Basic System With CommLink

2.)It Is Recommended That All

Controllers Address Switches Are

Set Before Installation.

3.)Power To The Zone Manager Must Be

Cycled Before Address Switch

Changes Will Take Affect.

RS-485

Communications To Zone

Controllers

Notes:

1.)AllCommunication Wiring To Be

2 Conductor Twisted Pair With

Shield. Use Belden #82760 Or

Equivalent.

R

SH

T

R

SH

T

R

SH

T

R

SH

T

All Comm Loop Wiring Is

Straight Thru

Local Loop

RS-485

9600 Baud