Setpoint screen #5a, Setpoint screen #5b, Setpoint screen #6 – Auto-Zone Control Systems Auto-Zone Basic Systems Installation & Operation (Version 02C) User Manual

Page 80: Auto-zone basic

Advertising
background image

Section 3

Auto-Zone Basic

3-12 Programming

Setpoint Screen #5A

Minimum

Default Maximum

PD Zone Vent Mode Min

0%

50%

100%

PD Zone Nite Mode Min

0%

100%

100%

Setpoint Screen #5B

Minimum

Default Maximum

PI Zone Vent Mode Min

0 CFM

500 CFM

30000 CFM

PI Zone Nite Mode Min

0 CFM

0 CFM

30000 CFM

PI Zone CFM @1" WG

0 CFM

2100 CFM

30000 CFM

Setpoint Screen #6





On Pressure Dependent Zones, the setpoints displayed are for
damper position.

PD ZONE ADDRESS 1

Vent Mode Min.: 50%

Nite Mode Min.: 100%

For Pressure Independent Zones the text changes to display
airflow (CFM) values. On the third line - "CFM@1" WG",
enter the appropriate "K" Flow Factor from Table 1-2 of this
manual.

PD ZONE ADDRESS 1

Vent Mode xxxxx CFM

Nite Mode xxxxx CFM

CFM @1”WG xxxxx CFM

PD ZONE ADDRESS 1

Overrides..: Global

Damper Mode: Direct

PRESS (*) TO TOGGLE

The Zone Controller will respond to another zone’s push-
button override if it is configured for global overrides. If single
overrides
are selected, the zone will only enter override if its
own push-button is pressed.

The normal damper operation is direct acting, which means it
opens in a clockwise direction. If your system opens in a
counter-clockwise direction, select reverse acting mode.

Advertising