Auxiliary heat control options – Auto-Zone Control Systems Auto-Zone Basic Systems Installation & Operation (Version 02C) User Manual

Page 23

Advertising
background image

Auto-Zone Basic

Section 1

Design Guide

1-17

Auxiliary Heat Control
Options

The Auto-Zone Basic Control System offers you a variety of methods to deal with zone
heating requirements. When deciding how to handle zone heating requirements, you
should consider the following:

• Does the rooftop unit have heat?
• Are you using fan-powered boxes?
• Is auxiliary heat used such as baseboard or radiant ceiling panels?

If the zone has some type of heat, you must consider how the heat is to be used. Typical
questions that should be asked:

Q: Should the zone heat be used as a first stage where it will become active before a

heating demand is created at the rooftop unit?


A: This mode is useful if you expect to have both heating and cooling demands at the

same time. The zone will use its own heat and allow the rooftop unit to continue to
provide cooling for other zones. This mode is also useful if the rooftop unit does not
have any heating capabilities.

Q: Is the zone heat only to be used as a second stage where it will be activated only if

the rooftop unit cannot maintain the space temperature such as during very cold
weather?


A: In this mode of operation the rooftop will examine the heating and cooling demands

and try to satisfy all of the zones by switching between heating and cooling as
required. The zone heat will only be activated if the zone temperature falls below a
selected limit.

Q: Should the zone heat be locked out if the rooftop unit is supplying warm air?

A: In many instances, it is desirable to use the rooftop heating whenever possible and

only use zone heat when the rooftop unit is in cooling or vent mode. This often
provides the most cost-effective operation since zone heat is typically electric. This
mode of operation will lockout zone heat if the rooftop is delivering heated air.

Advertising