Setpoint screen #2, Setpoint screen #3, Setpoint screen #4 – Auto-Zone Control Systems Auto-Zone Basic Systems Installation & Operation (Version 02C) User Manual

Page 79: Auto-zone basic

Advertising
background image

Auto-Zone Basic

Section 3

Programming 3-11

Setpoint Screen #2

Minimum

Default

Maximum

Cool Setback

0

°F 10°F 30°F

Heat Setback

0

°F -10°F -30°F

Setpoint Screen #3


Minimum

Default

Maximum

AuxHeat Setpt

50

°F 72°F 90°F

Slide Effect

0

°F 3°F 5°F


Note: If slide effect is set to 0°, the push-button override will not function.

Setpoint Screen #4

Minimum

Default

Maximum

PD Zone Max Damper
PI Zone Max Airflow

0%

0 CFM

100%

800 CFM

100%

30000 CFM

PD Zone Cool Mode Min
PI Zone Cool Mode Min

0%

0 CFM

5%

200 CFM

100%

30000 CFM

PD Zone Heat Mode Min
PI Zone Heat Mode Min

0%

0 CFM

20%

300 CFM

100%

30000 CFM

Enter the Unoccupied Heating and Cooling Setback values on
this screen. The Occupied Cooling Setpoint will be increased
by the Cooling Setback during Unoccupied Mode and the
Heating Setpoint will be decreased by the Heating Setback.

PD ZONE ADDRESS 1

UNOCCUPIED SETPOINTS

Cool SetUp...: 10 F

Heat Setback.: -10 F

If your Zone Controller has the optional Relay Expansion Board
attached, one of the relays is reserved for an Auxiliary Heating
Relay. Enter that setpoint on the AuxHeat Setpt line. If the
relay board is not installed, this line will not be displayed.

If your Zone Temperature sensor has the optional Setpoint
Adjustment Slide, enter the maximum effect it can have on the
setpoints on the Slide Effect line.

PD ZONE ADDRESS 1

AuxHeat Setpt: 72 F

Slide Effect.: 3 F

PD ZONE ADDRESS 1

Max Damper....: 100%

Cool Mode Min.: 5%

Heat Mode Min.: 20%

On Pressure Dependent Zones, these setpoints are for damper
position. On Pressure Independent Zones they are for Airflow
(CFM) values, and the text will change to reflect that.