Auto-Zone Basic

Section

4

Start-Up & Troubleshooting

4-11

Zone Controller Wiring

Correct wiring of the Zone Controller is critical to proper system operation. If compo-
nents are wired to the wrong inputs, the system will not operate correctly or will not op-
erate at all. Correct wiring of the 24VAC power is extremely critical. If voltage greater
than 24VAC is applied to the terminal, it will damage the board beyond repair
. It is rec-
ommended that a separate transformer be used for each Zone Controller. If one trans-
former is used to power multiple Zone Controllers, all 24VAC wiring must be connected
so that all ground wires remain common. DO NOT REVERSE POLARITY
BETWEEN CONTROLLERS
. Failure to comply with this will also result in damage to
the board. See Figure 4-9. Also see Section 2 of this manual for more detailed wiring
instructions and procedures.

Figure 4-9: Zone Controller Wiring