Section 3

Auto-Zone Basic

3-4 Programming

Status Screen #3







Status Screen #4

Line 2 - Current Zone Damper Position

Line 3 - Currently active Minimum Damper/Airflow

Setpoint. Each mode has its own minimum setpoint.
These modes are vent, cooling and heating.

Line 4 - Currently active Maximum Damper/Airflow

Setpoint. This value is user adjustable and is used in
all modes of operation, unlike the Minimum
Damper/Airflow Setpoint.

Zone Number 1

Damper Pos 20

Minimum Setpt 20

Maximum Setpt 100

Line 2 -

Auxiliary Heat Off
Box Heating On
Aux Heating On
Box & Aux Heat On

Line 3 -

Series Fan On
or
Blank Line if Fan is Off

Line 4 -

Parallel Fan On
or
Blank Line if Fan is Off

Zone Number 1

Auxiliary Heat Off

Series Fan On