Setpoint screen #7, Setpoint screen #8 – Auto-Zone Control Systems Auto-Zone Basic Systems Installation & Operation (Version 02C) User Manual

Page 81

Advertising
background image

Auto-Zone Basic

Section 3

Programming 3-13

Setpoint Screen #7


Setpoint Screen #8



Note: The Thermistor Type III Sensors have a 0.4 degree accuracy.

Tip: This calibration offset is also useful as a troubleshooting tool. If you need to

simulate a heating or cooling mode, you can raise or lower the current zone
temperature far enough to put the zone into the desired mode.

Caution: The normal calibration offset should be a fairly small value. If you need

several degrees of offset, there might be a sensor problem or a location
problem.

PD ZONE ADDRESS 1

Voting Mode: Voting

PRESS (*) TO TOGGLE

Normally, you want a zone to be included in the polling by the
Zone Manager. This allows the demand in that zone to have a
vote in determining the HVAC mode of operation. If you have
a problem zone or an area that you don't want to include in the
voting, select the NonVote mode of operation.

PD ZONE ADDRESS 1

Sensor Calibration

Rdg Offset

Zone: 75.4 0.0

If you have a tenant that doesn't agree with the current zone
temperature reading, you can adjust or calibrate the zone
temperature reading
.
Enter a positive number if the current reading is too low.
Enter a negative number if the current reading is too high.

Advertising