Room Sensors

The Room Sensor uses a patented flush-mount design to isolate the temperature sensing
element from the housing which mounts flush with the wall surface.

Room Sensors should be located on an inside wall away from direct sunlight or heat-
producing equipment such as computers, copiers, etc. Such devices can adversely affect
the accuracy of the sensor. Although the sensor eliminates most of the effects of thermal
coupling to the walls, try to avoid walls which retain large amounts of thermal energy
(such as marble or steel). Walls containing either cold or warm air currents should also be
avoided whenever possible. Avoid locating the sensor in dead air areas of a room. This
will result in slow response to temperature changes in the space.

Figure 2-15: Room Sensor Installation

Mount the sensor approximately 50-60 inches from the floor for best results. The Room
Sensor is designed to mount vertically in a standard 2- by 4-inch electrical box. The sen-
sor may be mounted directly into the drywall where electrical codes do not require low
voltage wiring to be enclosed in conduit. A template is supplied with the sensor to facili-
tate cutting a hole of the correct size.

Tip: Be careful when cutting the hole to make sure the sensor or the plastic bezel of

the sensor will completely cover the opening.

Tip: If sensors must be installed on walls which are solid and cannot be penetrated,

surface-mounted boxes and raceway can be purchased from your local electrical
distributor.