Outside Air Temperature Sensor

The outside air sensor must be located where it will not be affected by direct sun or heat
producing equipment. Mounting under the eve of a roof is often a good choice.

Caution: Complaints of inaccurate outside sensor readings are very common and

can almost always be shown to be the result of poor sensor location.


Note: All sensors utilize the same type thermistor sensor element. For troubleshooting

sensors, refer to temperature sensor resetting instructions in section 3 of this
manual.

Figure 2-18: Outside Air Temperature Sensor Dimensions and Installation

4.)All Wiring To Be In Accordance With

Local And National Electrical Codes
And Specifications.

3.)Gasket Must Be Installed Under Cover

Plate To Provide Raintight Seal.

Rainwater Can Damage Sensor!

2.)Unused Conduit Opening(s) Must

Have Closure Plugs Installed And Must
Be Coated with Sealing Compound To
Provide Raintight Seal. Water Can

Damage Sensor!

1.)The Outside Air Sensor Must Be

Mounted In A Vertical Position As
Shown (Sensor Tube Pointing
Down).

Sensor Must Be Located

Where It Will Not Be Affected By
Direct Sunlight Or Heat Producing
Equipment. If Possible Mount Under
Roof Eave Or Similar Protected
Location. If Sensor Is Not Located
As Specified, Erroneous Outside Air
Temperature Readings Will Result.

Water Must Not Be

Allowed To Stand In Sensor

Tube. Rainwater Will Damage

Sensor.

Notes:

Closure Plug

CAUTION!

See Note 2

Gasketed Cover

CAUTION!

See Note3

Cover
Mounting
Screw - Typ.

Mounting Tab
& Screw - Typ.

0.21" Dia. x 0.73
Lg. Slot - Typ.

4.50”

2.25”

3.00”

Front View

Side View

Back View

Closure Plug

CAUTION!

See Note 2

Sensor Tube

CAUTION!

See Note 1

Mounting Tab
& Screws - Typ.

Correct

Incorrect

Incorrect

See Note #1

Sensor Mounting

Postion

2.70”

1.13”

2.30”

3.00”

Advertising