Configuration screen #2, Configuration screen #3, Configuration screen #4 – Auto-Zone Control Systems Auto-Zone Basic Systems Installation & Operation (Version 02C) User Manual

Page 89

Advertising
background image

Auto-Zone Basic

Section 3

Programming 3-21

Configuration Screen #2











Configuration Screen #3


Configuration Screen #4


Heat Type.: Electric

Fan Mode.: Constant

PRESS (*) TO TOGGLE

Economizer: Enabled

PRESS (*) TO TOGGLE

HVAC Type: Variable

PRESS (*) TO TOGGLE

The Zone Manager can control electric or gas heating. Each
type of heat has its own protection limits built into the Zone
Manager software.

The Zone Manager can also operate the fan in one of two
modes:

Constant (Continuous) running during occupied hours.

Cycle with heating or cooling during occupied hours.

The fan always cycles with heating or cooling during
unoccupied hours.

The Zone Manager has the ability to control the Economizer
operation. To initiate Economizer operation, select Enabled.
To toggle between the two Economizer modes, press the "*"
key.

The Zone Manager normally reads the duct static pressure
and controls it via the bypass damper. If your system doesn't
require static pressure control, select the Constant mode of
operation. To toggle between the two modes, press the "*"
key.