Section 3

Auto-Zone Basic

3-20 Programming

Zone Manager
Configuration

Normally, the configuration setpoints need to be entered only one time. For this reason,
they occupy their own menu location and need not be addressed during normal setpoint
read and reset operations. To access the configuration setpoints, press the "3" key while
on the Main Menu screen.

Note: On initial power up, the system must be configured before it can be successfully

operated.

Configuration Screen #1

Minimum

Default

Maximum

Last Zone Addr

1 1 16

First Zone Addr

1

1

16

Cooling

Stages 0 1 6

Heating

Stages 0 1 6

Caution: The zones should be consecutively addressed with no skipped address

locations. If an address is skipped, the Zone Manager will presume there
is a missing zone, and an alarm will occur.

The Zone Manager needs to know the address range of the
attached Zone Controllers to be polled
. Enter the addresses of
the first and last zones here.

The quantity of cooling and heating stages is also entered on
this screen.

Last Zone Addr: 1

First Zone Addr: 1

Cooling Stages: 1

Heating Stages: 1