Auto-Zone Basic

Section 2

Installation and Wiring

2-27

Tip: Having at least 10-20 feet of tubing between the pick-up tube and the pressure

sensor will improve control performance by acting as a “filter” to remove pres-
sure fluctuations caused by turbulence in the duct.



Figure 2-20: Static Pressure Sensor Wiring


Note:
Refer to Figure 1-3 in section 1 of this manual for instructions concerning

proper location of the static pressure sensor.