Section 4

Auto-Zone Basic

4-22

Start-Up and Troubleshooting

Some zones are communicating but others are not:

• Is the Zone Manager set for the correct number of zones?
• Are the Zone Controller address switches set correctly? See the addressing chart.
• Are the Zone Controllers powered? Check 24VAC to the controllers.
• Is the REC LED on the missing Zone Controller “flickering”? See Zone Control-

ler introduction for location of the REC LED.

• Is the SCAN LED blinking an error code? See the BLINK CODE chart.
• Are COMM LOOP voltages correct at the missing unit? See the COMM LOOP

troubleshooting guide.